Power Supply - Single or three phase units; 220-240 VAC ±10%;
50-60 Hz ±5%
Three phase units; 380- 460 VAC ±10%; 50-60 Hz ±5%
Ambient - Constant Torque rating - 0-45°C
(32-113°F) (40°C (104°F) with IP40 cover); Variable Torque rating
- 0-40°C (32-104°F) (35°C (95°F) with IP40 cover); derate 2%
per °C to 50°C (122°F) maximum
Altitude - 1000m (3280 ft.) ASL; derate 1% per 100m (328 ft.)
above 1000m (3280 ft.) to 5000m (16400 ft.) max.
Overload - 150% for 60 seconds, 180% for 0.5 second (frames
C through F only) (constant torque rating) 115% for 60
seconds (variable torque rating)
Output Frequency - 0-480 Hz
Switching Frequency - Frame B 3, 6 or 9 kHz; Frame C, D, E
and F 3 or 6 kHz (all with audibly silent switching pattern)
Environmental Protection - IP20
Inputs/Outputs
Analog Inputs - 4; User configurable (10 bit (12 bit with systems
expansion module) (0-10V, ±10V, 0-20mA, 4-20mA))
Analog Outputs - 3; User configurable (10 bit 0-10V, ±10V,
0-20mA, 4-20mA)
Digital Inputs - 7; User configurable (nominal 24V DC)
Digital Outputs - 3; User configurable relay outputs (3A @
230 VAC)
Motor Thermistor Input
Standards
The 690+ series meets European and North American standards
when installed in accordance with relevant product manual.
Options & Accessories
Miscellaneous: Remote mounting bezel and 3m (10 ft.)
lead 6052
Technology Boxes:
690+ Size B
690+ All Others
Profibus:
6053/PROF/00
6055/PROF/00
Modbus/RS422/RS485/EIBisynch
6053/EI00/00
6055/EI00/00
Link
6053/LINK/00 6055/LINK/00
DeviceNet
6053/DNET/00
6055/DNET/00
Encoder feedback
LA467461
6054/00
Wall Mount IP40 (NEMA 1) Covers - included to 60 Hp (not
available above 60 Hp)
Dynamic Braking Switch - optional above 15 Hp (replace the
‘B’ in the part number with a ‘N’ to remove this option)
For example, change 690+0020/460/1BN to 690+0020/460/1NN for
a standard, 20 Hp, 690+ controller without a Dynamic Braking
Switch installed. Drives do not include resistors for
braking, for details on resistors, click
here.
System Expansion Module - Factory installed option.
(Replace the ‘N’ in the part number with a ‘S’ to select this
option.) For example, change 690+0020/460/1BN to 690+0020/460/1BS
for a standard, 20 Hp, 690+ controller with a System Expansion
Module installed.
Internal EMC filter (up to 10 Hp): (Add a ‘-F’ suffix to select
this option) For example, change 690+0005/460/1BN to 690+0005/460/1BN-F
for a 5 Hp, 690+ controller with an internally mounted EMC filter.
Click here for optional external
EMC filters and line chokes.