Notes: Powers and currents in parentheses () are user
quadratic "fan" torque ratings. "V"
suffix drives denotes high torque sensorless vector unit.
This is optional from 0.2 to 7.5kW and standard at 11kW and above.
Model Number Options
Remote mount keypad and Serial port standard on all 650V model
drives (for frames 1, 2, and 3, select 650V and replace the
‘S’ in the part number with a ‘R’ to select this option)
For example, change 650/0010/460/SBN to 650V/0010/460/RBN for
a standard, 10 Hp, 650 sensorless vector controller with a remote
mountable keypad.
Brake Switch (optional above 15 Hp) (replace the ‘B’ in the
part number with a ‘N’ to omit this option) For example,
change 650V/0040/460/SBN to 650V/0040/460/SNN for a standard,
40 Hp, 650 sensorless vector controller with a brake switch.
Internal EMC filter (up to 10 Hp) (replace the ‘N’ in the part
number with a ‘F’ to select this option) For example,
change 650/0010/460/SBN to 650V/0010/460/SBF for a 10 Hp, 650
sensorless vector controller with an internally mounted EMC
filter.
For external footprint style EMC filters (15 to 150 Hp), click
here.
Technical Specification
Power Supply
Single phase units; 220-240 VAC ±10%; 50-60 Hz ±5%
Three phase units
380-460 VAC ±10%; 50-60 Hz ±5%
Ambient
0-40°C (32-104°F); derate 2% per °C to 50°C (122°F) maximum
Altitude
1000m (3280 ft.) ASL; derate 1% per 100m (328 ft.) above 1000m
(3280 ft.) to 5000m (16400 ft.) max.
Overload
150% for 30 seconds (heavy duty)
115% for 30 seconds (standard duty)
Output Frequency
0-240 Hz
Environmental Protection
IP20
Inputs/Outputs
Analog Inputs - 2; Speed control (0-10V, 4-20mA)
Analog Output - 1; User configurable:
DEMAND
CURRENT
PID ERROR
RAISE-LOWER OUTPUT (0-10V)
Digital Inputs - 2; User configurable:
start
stop
direction
pre-set speeds (8)
Digital Input/Outputs - 2; User configurable as inputs or outputs
Digital Relay Outputs - 1; User configurable relay outputs
(1A @ 240V)
All digital outputs configurable for:
AT SPEED
AT ZERO SPEED
RUNNING
HEALTHY
TRIPPED
Motor Thermistor Input
Standards
The 650 series meets European and North American standards
when installed in accordance with relevant product manual.